Sound insulation testing: the Part E pass marks and what a test costs
Updated
Regulation 41 (Building Regulations 2010) requires on-site sound insulation testing of walls and floors between homes against Part E. Three UK testers in our index publish prices, £199.95 to £450.
Get assessment quotes Two minutes of questions; relevant acoustic consultants quote you directly. Free, no obligation.
For a new-build wall or floor, Part E means at least 45 dB airborne insulation and at most 62 dB impact sound through a floor. For a conversion the figures are 43 dB and 64 dB.
When the law requires it
Regulation 41 applies to building work where paragraph E1 of Schedule 1 imposes a requirement. That covers walls and floors separating dwellings, including those created by a material change of use.
The person carrying out the work must have sound insulation testing carried out by an approved procedure. They must give the results to the building control authority (regulation 41, legislation.gov.uk).
The test is skipped only where a new house or block of flats is built to a design detail approved by Robust Details Limited. Building control must be told before work starts. In England this applies as amended; Wales has its own version.
The standards a test must reach
| Building | Element | Airborne, DnT,w + Ctr (minimum) | Impact, L'nT,w (maximum) |
|---|---|---|---|
| Purpose built houses and flats | Walls | 45 dB | Not tested |
| Purpose built houses and flats | Floors and stairs | 45 dB | 62 dB |
| Formed by material change of use | Walls | 43 dB | Not tested |
| Formed by material change of use | Floors and stairs | 43 dB | 64 dB |
Approved Document E says the values already allow for measurement uncertainty, so a test that misses one by any margin has failed (Approved Document E, para 1.6). Rooms for residential purposes, such as hotel rooms and student rooms, have their own table, with 43 dB for a purpose built wall.
How many tests a site needs
- In flats with a separating floor and wall, a set is normally six individual tests: airborne tests across a separating wall in two pairs of rooms, and airborne and impact tests across a separating floor in two pairs of rooms (para 1.21). Testing a full set in flats needs access to at least three flats (para 1.22).
- Building control asks for one set between the first homes completed in each group or sub-group of the same construction, however small the group, so a site of only one pair of homes is still tested (para 1.29).
- After that, assuming no failures, at least one set for every ten homes in a group (para 1.30), with more testing early in a run of completions than at the end (para 1.31).
- Testers should preferably hold UKAS accreditation for field measurements, and members of the Association of Noise Consultants' Registration Scheme are also regarded as suitably qualified (para 0.4).
What a test costs
| Tester | Published price |
|---|---|
| Easy EPC | £199.95 |
| UK Building Compliance | £375 |
| ACA Acoustics | £450 |
Each figure is the tester's own starting price as published. What it covers (one set or one test, travel, the report) differs from firm to firm, and most testers publish no price at all.
A failed test adds remedial work and a retest. Approved Document E warns that if the cause is the construction, untested rooms may fail too (para 1.38). Booking the first set early is cheaper than finding a problem at the last plot.
What to ask a tester
- Are you UKAS accredited for field sound insulation testing, or a member of the ANC Registration Scheme?
- Does the price cover a full set of tests, and how many plots or units does that cover?
- Will you agree the testing plan with my building control body?
- What happens, and what does it cost, if a test fails?